Building maintenance and construction work requiring effective fire safety planning
Workplace Fire Safety

How to Manage Fire Risks During Building Maintenance Work

A practical guide to hot work, contractor safety, fire protection systems, risk assessments and maintenance checklists for safer buildings.

Fire Prevention & Risk Management Practical Safety Guide For Facilities Managers & Contractors

Building maintenance is essential for keeping commercial premises, workplaces and public buildings safe and operational. However, repair and refurbishment work can introduce new fire hazards. Welding can produce sparks, electrical work can create ignition sources, combustible waste can accumulate, and maintenance may temporarily affect fire alarms, sprinklers, fire doors or escape routes.

Knowing how to manage fire risks during building maintenance work helps building owners, facilities managers, contractors and employers prevent fires while protecting workers, visitors and other occupants. Effective fire prevention requires more than keeping a fire extinguisher nearby. It requires risk assessment, careful planning, suitable supervision and checks that fire protection arrangements remain effective throughout the work.

This guide explains practical fire safety procedures, contractor controls, hot work precautions and a building maintenance fire safety checklist. It also identifies common mistakes and explains what should happen before maintenance begins, while the work is underway and before the building is handed back.

Key takeaway: Before maintenance starts, identify what could ignite, what could burn, who could be affected and which fire safety measures could be compromised. Put suitable controls in place, monitor them throughout the job and verify that affected systems and building features are safe before signing off the work.
Metalworking and hot work activity illustrating the need to control sparks and ignition sources
Hot work controls
Assess sparks, heat, combustible materials and concealed spaces before authorising high-risk work.
Technical maintenance work requiring competent personnel and safe working procedures
Planned maintenance
Coordinate competent workers, safe equipment, permits and building access arrangements.
Engineer carrying out technical inspection work as part of a maintenance safety process
Inspection and verification
Check that work is complete and affected safety arrangements are restored.
Building safety and fire alarm equipment relevant to fire detection and emergency preparedness
Fire protection systems
Control impairments and verify that detection and warning arrangements operate correctly.

What Does Managing Fire Risks During Building Maintenance Mean?

Managing fire risks during building maintenance means identifying potential ignition sources, combustible materials and conditions that could allow a fire to start or spread, then implementing suitable precautions before work begins.

The process includes reviewing the fire risk assessment, coordinating contractors, controlling hazardous activities, protecting escape routes, managing temporary fire system impairments and confirming that affected areas are safe after the work.

For example, replacing a ceiling may expose electrical cables, disturb fire-stopping materials or create openings between compartments. Welding a metal support may introduce sparks that reach concealed combustible materials. Servicing a fire alarm may temporarily affect detection in part of a building.

These activities require different precautions. A suitable maintenance fire safety plan should address three main objectives:

  • Prevent ignition: eliminate or control heat sources, electrical faults, open flames and other potential causes of fire.
  • Limit fire and smoke spread: protect compartmentation, manage combustible materials and maintain fire doors and barriers.
  • Protect people: keep warning systems, escape routes and emergency arrangements effective.

Why Is Fire Safety Important During Building Maintenance?

Maintenance can temporarily change the conditions under which a building’s fire safety arrangements were designed to operate. A building with effective alarms, protected escape routes and fire-resisting construction may become more vulnerable if these safeguards are disturbed without suitable controls.

Hot work can introduce ignition sources

Welding, brazing, soldering, grinding, flame cutting and torch-applied roofing can produce flames, sparks or hot particles. These may ignite packaging, insulation, timber, dust, plastics or combustible materials hidden behind walls and ceilings. Sparks and heat can also travel through openings and concealed spaces.

Electrical maintenance can create fire hazards

Damaged cables, overloaded temporary supplies, loose connections and faulty equipment can cause overheating or arcing. Electrical work should be planned and performed by appropriately competent personnel using suitable isolation and testing procedures.

Fire protection systems may be impaired

Maintenance may require temporary isolation of a fire alarm zone, sprinkler installation, smoke-control system or other protective equipment. During an impairment, the building may have less capacity to detect, warn about or control a fire.

Escape routes and fire doors can be obstructed

Tools, ladders, replacement materials and waste can block corridors, stairs and exits. Removing a fire door or leaving it wedged open can compromise protection against smoke and fire spread.

Combustible waste can accumulate

Packaging, insulation offcuts, sawdust, solvent-contaminated materials and discarded components may increase the fuel available for a fire. Removing waste promptly helps reduce this risk and keeps access routes clear.

Common Fire Hazards During Building Maintenance

Before selecting control measures, identify the hazards associated with the actual task, the building and the people who may be affected.

Maintenance activityPotential fire hazardRecommended control
Welding, cutting or grindingSparks, hot metal and ignition of nearby combustiblesAssess the task, authorise hot work where required, remove or protect combustibles and arrange monitoring.
Electrical repairsShort circuits, arcing, overheating and damaged wiringUse competent personnel, suitable isolation and safe electrical work procedures.
Roof repairsHot-applied materials, gas cylinders and combustible roof componentsAssess roof construction, control ignition sources and protect vulnerable materials.
Painting and decoratingFlammable vapours, solvents and contaminated clothsFollow product safety information, provide suitable ventilation and control ignition sources.
Ceiling or partition workDamaged fire stopping and openings through compartmentsIdentify concealed services and restore fire-resisting construction using suitable systems.
Fire alarm servicingReduced detection or warning during isolationAuthorise the impairment, assess the risk, implement suitable temporary precautions and verify restoration.
Sprinkler or pipework maintenanceReduced fire suppression coverageMinimise the impairment, assess the risk and coordinate suitable alternative precautions.
Storage and waste removalAccumulated combustible materials and ignition opportunitiesUse designated storage areas and remove waste at appropriate intervals.

How to Manage Fire Risks During Building Maintenance Work

A structured process makes fire safety easier to implement, monitor and document. The following steps can be adapted for routine repairs, planned maintenance, refurbishment projects and specialist contractor activities.

  1. Review the existing fire risk assessment

    Before work begins, review the building’s current fire risk assessment and determine whether the proposed maintenance introduces new hazards or changes existing risks. Consider the work location, equipment, substances, combustible materials, concealed spaces, escape routes, fire doors, alarm systems and the people occupying the building.

    For example, installing lighting above a suspended ceiling may expose damaged wiring or disturb fire-stopping materials. The assessment should identify these possibilities and establish suitable precautions before work proceeds.

    Review the assessment whenever the task, work location, equipment, occupancy or fire protection arrangements change materially. Do not rely on an outdated assessment that no longer reflects site conditions.

  2. Identify everyone who could be affected

    Fire safety planning must consider employees, contractors, cleaners, security staff, visitors, customers, residents and people who may need assistance to evacuate. Identify where these people will be while maintenance takes place and whether temporary changes could affect their ability to recognise a warning or reach safety.

    Additional planning may be needed in hotels, healthcare settings, occupied residential buildings, public areas and premises where people are unfamiliar with the layout. Coordinate alternative access, communication and evacuation arrangements when necessary.

  3. Prepare a task-specific fire safety method

    A maintenance plan should explain how the work will be completed safely. Depending on the risk, it may form part of a risk assessment, method statement or permit-to-work process.

    • Define the scope, location and timing of the work.
    • Identify equipment, substances and potential ignition sources.
    • Specify isolation and reinstatement arrangements.
    • Establish hot work authorisation where applicable.
    • Plan combustible material removal and protection.
    • Identify fire system impairments and emergency arrangements.
    • Set inspection, monitoring and handover responsibilities.

    The level of detail should reflect the actual risk. A signed document is not proof that a site is safe: supervisors must verify that the required precautions are in place.

  4. Control hot work with a permit-to-work system

    Hot work is one of the most important activities to control because it can introduce intense heat and sparks into areas that were not previously exposed to such ignition sources. Examples include welding, flame cutting, grinding, brazing and some roofing operations. Personnel involved in these activities can develop relevant safety knowledge through the ICTQual Level 1 Award in Naked Flame, Hot Work and Fire Watcher.

    Where a hot work permit system is used, it should formalise the assessment, precautions, authorisation and post-work checks.

    • Consider alternatives. Determine whether cold cutting, mechanical fastening or another method can avoid hot work.
    • Inspect the area. Identify combustibles, openings, concealed voids, flammable substances and routes through which sparks or heat could travel.
    • Remove or protect combustibles. Clear the work area where practicable and use suitable protection where materials cannot be removed.
    • Check adjacent spaces. Inspect relevant rooms, the opposite side of walls, areas below the work and concealed spaces.
    • Provide precautions. Confirm that suitable firefighting equipment, communication and monitoring arrangements are available as required.
    • Authorise and supervise. Verify the controls before starting and stop work if conditions change or precautions fail.
    • Inspect after completion. Check the work area and relevant surrounding spaces for heat, smoke or smouldering materials.

    A permit is not a substitute for competent supervision or a proper assessment. The required fire-watch duration and inspection frequency should be based on the task-specific risk assessment and site conditions, rather than assuming one fixed period suits every job.

    Read the HSE guidance on fire safety in construction (HSG168) for further information about managing fire risks during construction-related work.

  5. Manage flammable liquids, gases and combustible materials

    Maintenance activities may involve paints, adhesives, cleaning agents, fuels, solvents, sealants, insulation, plastics and gas cylinders. Their risks depend on their properties, quantities, storage conditions and intended use.

    • Keep only the quantities required for the task in the work area.
    • Store flammable products in appropriate designated locations.
    • Follow product instructions and relevant safety data sheets.
    • Prevent leaks, spills and uncontrolled releases.
    • Provide suitable ventilation where vapours may accumulate.
    • Control smoking, naked flames and other ignition sources.
    • Secure gas cylinders and protect them from damage and heat.
    • Dispose of contaminated cloths and hazardous waste safely.

    A substance that presents limited risk under normal conditions may become hazardous when heated, sprayed, spilled or used in a poorly ventilated area. Consider storage and handling alongside the wider fire risk assessment.

  6. Maintain safe electrical working practices

    Electrical maintenance may involve distribution boards, sockets, wiring, lighting, heating equipment, motors and temporary power supplies. Damaged insulation, loose connections, overloading and arcing can create fire risks.

    Ensure electrical work is carried out by appropriately competent personnel. Use suitable isolation and lockout procedures where required, verify equipment is safe before work begins, inspect tools and leads, and remove damaged equipment from service.

    Temporary cables must not introduce hazards in corridors or escape routes. Before drilling or cutting walls, floors and ceilings, establish the location of concealed cables and services. Where work affects fire alarms, emergency lighting or smoke-control systems, coordinate it with the responsible building personnel.

  7. Protect fire detection and alarm systems

    Fire detection and alarm systems are essential for warning people when a fire occurs. Maintenance, refurbishment, dust and electrical work can affect their operation or cause unwanted alarms.

    Before isolating or testing equipment, obtain the required authorisation, identify the affected devices or zones, inform relevant personnel and assess whether occupants will remain in the area. Determine whether temporary detection, fire patrols or other suitable precautions are needed.

    Keep the impairment as short as reasonably practicable and establish how an emergency will be raised. If adequate protection cannot be maintained, the affected activity or occupancy may need to be restricted until suitable protection is restored.

    After maintenance, confirm that affected equipment is back in service, required tests are satisfactory, faults are addressed and relevant parties are informed. Never assume a system is operational simply because the contractor has left.

  8. Keep fire doors, compartmentation and escape routes effective

    Fire doors, fire-resisting walls, floors, service penetrations and protected routes help limit fire and smoke spread. Maintenance can compromise these protections when doors are removed, walls are drilled or pipes, cables and ducts are installed.

    • Identify fire-resisting construction before making penetrations.
    • Use suitable fire-stopping systems for the specific application.
    • Avoid leaving unprotected openings at the end of a shift.
    • Reinstate fire doors and associated hardware correctly.
    • Do not wedge fire doors open for convenience.
    • Keep corridors, stairs, exits and final exit doors clear.
    • Provide safe alternative routes where approved arrangements require them.

    Ordinary foam, filler or sealant should not be assumed suitable for fire stopping. Use a system appropriate to the required application and follow its installation requirements. Verify that affected fire-resisting elements have been restored before signing off the work.

  9. Manage contractors and communicate responsibilities

    Contractors may understand their trade but remain unfamiliar with the building’s fire strategy, evacuation arrangements and site-specific hazards. Contractor management should establish clear responsibilities before work begins and maintain communication throughout the task.

    Depending on the arrangements, responsibilities may include reviewing risk assessments, delivering inductions, authorising permits, coordinating contractors, monitoring housekeeping, reporting defects and confirming handover.

    Inductions should explain the alarm signal, evacuation routes, assembly arrangements, emergency contacts, restricted areas, smoking rules and hazard reporting procedures. Supervisors should check that workers understand the controls relevant to their tasks. A signed attendance sheet alone does not demonstrate understanding.

  10. Control housekeeping and combustible waste

    Building maintenance can produce packaging, dust, insulation offcuts, timber, cable insulation and discarded fittings. When these materials accumulate, they can increase the fuel available for a fire and obstruct access to emergency equipment.

    Remove unnecessary combustible waste regularly, use designated storage areas, separate waste types where required and handle oily rags or solvent-contaminated materials safely. Keep waste away from ignition sources and never store it in stairwells, corridors or plant rooms where it can obstruct evacuation or access to safety equipment.

    At the end of each shift, confirm that tools and equipment have been left in a safe condition, hazardous materials are secured and waste has been removed.

  11. Inspect the site throughout the work

    Fire risk management must continue after the initial assessment. Conditions can change as work progresses, ceilings are opened, materials are moved and different trades enter the area.

    Inspections may cover hot work permits, combustible storage, temporary electrical supplies, escape routes, fire doors, access to firefighting equipment, impaired systems, fire-stopping work, waste accumulation and changes to occupancy.

    Inspection frequency should reflect the level of risk and the duration of the work. If a control fails, stop the affected activity when necessary, address the hazard and do not restart until the required precautions are effective.

  12. Complete a formal fire safety handover

    The end of the maintenance task is not necessarily the end of its fire risk. Systems may remain isolated, doors may need adjustment, penetrations may require final inspection or faults may remain unresolved.

    Before closing the job, confirm that waste has been removed, required hot work checks are complete, escape routes are clear, fire doors and compartmentation have been reinstated, and affected fire protection systems have been restored and tested as required.

    Record outstanding defects, communicate restrictions, update relevant records and review the fire risk assessment if the work has materially changed the building or its risks. If adequate fire protection is unavailable, identify the restrictions and actions required before normal operation resumes.

Building Maintenance Fire Safety Checklist

Use this practical checklist as a starting point for planning and supervising maintenance. Adapt it to the building, the activity and the applicable fire safety requirements. You can tick the items as you complete your review.

Pre-work, during-work and handover checks

Important: This checklist supports but does not replace a task-specific fire risk assessment, a hot work permit or inspections and testing required for particular systems.

What If a Fire Protection System Must Be Disabled?

Sometimes maintenance cannot be completed without temporarily isolating part of a fire alarm, sprinkler installation, emergency lighting system or smoke-control arrangement. This creates an impairment that needs additional planning because the building may have reduced protection.

Before isolation

Identify the equipment affected, assess the consequences, obtain authorisation and establish suitable temporary precautions. Inform relevant occupants and personnel. Determine whether the work or occupancy needs to be restricted.

During isolation

Keep the impairment as short as reasonably practicable, monitor the affected area and ensure that people understand how an emergency will be raised. Coordinate any overlapping maintenance activities that could increase risk.

After restoration

Confirm that equipment is back in service, complete required tests, investigate outstanding faults and notify relevant personnel. Document the restoration and any remaining limitations.

Safety rule: If the risk cannot be controlled adequately while a fire protection system is unavailable, postpone the work or suspend the affected activity until suitable protection can be maintained. Do not rely on an undocumented verbal agreement.

Who Is Responsible for Fire Safety During Building Maintenance?

Responsibility depends on the building, the work being performed, contractual arrangements and applicable legislation. Several parties may have duties relating to the same premises or activity.

RoleTypical responsibilities
Building owner or responsible personEnsure relevant fire safety arrangements are suitable, maintained and reviewed.
Facilities or building managerCoordinate maintenance, access, system impairments and site communication.
Maintenance supervisorCheck work planning, required permits, precautions, inspections and handover.
Contractor or employerManage risks arising from the work, provide suitable instructions and ensure workers follow precautions.
Individual workerFollow instructions, use equipment safely and report hazards or unsafe conditions.
Fire safety or technical specialistProvide competent advice, inspection or testing within their area of expertise.

These descriptions are practical examples, not a universal allocation of legal duties. Actual responsibilities must be established for the premises and work arrangement.

In England and Wales, the Regulatory Reform (Fire Safety) Order 2005 sets out duties relating to fire risk assessment, general fire precautions and maintenance. Article 5 addresses duties in relation to the extent of a person’s control over premises. Requirements differ across jurisdictions, so organisations should consult the applicable local legislation and competent advisers.

Common Fire Safety Mistakes to Avoid

Assuming a small job is automatically low risk

A short repair can introduce sparks, expose electrical faults or compromise fire-resisting construction. Assess the actual task rather than relying on its duration or apparent simplicity.

Starting hot work before the area is prepared

Beginning welding or grinding before combustible materials have been removed, adjacent spaces checked and required precautions verified can create avoidable ignition risks.

Disabling alarms without an impairment plan

An undocumented isolation can leave occupants without effective warning. Relevant impairments should be authorised, assessed, communicated and managed until restoration.

Leaving fire doors open for convenience

Wedging doors open or removing them without appropriate arrangements may undermine compartmentation and allow smoke to spread more easily.

Allowing waste to accumulate

Packaging, insulation and other waste can increase the fuel available for a fire. Maintain housekeeping throughout the job rather than postponing it until the end.

Failing to inspect after hot work

Sparks and heat may ignite concealed materials after the task is finished. Follow the task-specific fire-watch and inspection requirements before closing the permit.

Assuming the contractor alone is responsible

The contractor has responsibilities for the work, but building management and other parties may also have duties within their control. Effective coordination is essential.

Signing off work without verifying reinstatement

A completed repair does not automatically mean the fire protection system is operational. Confirm the required inspections, testing, reinstatement and documentation before declaring the task complete.

How Can Organisations Improve Fire Safety During Planned Maintenance?

Organisations can improve fire safety by integrating risk management into the wider facilities management process rather than treating it as a separate paperwork exercise.

  • Maintain accurate records. Keep an up-to-date register of fire safety systems, inspections, known defects and previous impairments.
  • Plan work in advance. Identify activities that may affect fire protection or occupied areas and arrange suitable precautions before contractors arrive.
  • Use permit-to-work procedures. Establish clear controls for higher-risk activities, including hot work and significant fire system impairments.
  • Brief contractors and staff. Use inductions and toolbox talks to reinforce the controls relevant to each activity.
  • Encourage hazard reporting. Make it straightforward to report near misses, defects and changing site conditions.
  • Review recurring problems. Use inspection findings to improve maintenance planning, contractor selection and supervision.
  • Verify competence. Ensure that those carrying out and checking specialist work have the appropriate knowledge and skills.

For further guidance, consult the HSE’s fire safety in construction publication and the government’s fire safety risk assessment checklist.

Frequently Asked Questions

How do you manage fire risks during building maintenance work?

Review the fire risk assessment, identify task-specific hazards, plan suitable controls, coordinate contractors, manage hot work and combustible materials, protect escape routes and control fire protection system impairments. Inspect the site throughout the work and complete a handover confirming that the area and affected systems are safe.

What is the biggest fire risk during building maintenance?

There is no single biggest risk for every task. Hot work can introduce sparks and intense heat, electrical work can create ignition hazards, and maintenance affecting alarms or compartmentation can reduce existing protection. The most significant risk depends on the task, materials, building layout and people affected.

Is a hot work permit necessary for building maintenance?

A hot work permit is an important control for tasks such as welding, cutting and grinding that may ignite combustible materials. Whether a formal permit is required depends on the organisation’s procedures, site conditions, the work and applicable requirements. Where used, the permit should specify precautions, authorisation and post-work checks.

What should be checked before starting maintenance work?

Review the risk assessment, inspect the work area, identify combustible materials and ignition sources, confirm contractor induction, check escape routes and establish the condition of relevant fire protection systems. Verify that required permits, isolations and temporary safety measures are in place.

How should fire alarms be managed during maintenance?

Any planned isolation or impairment should be authorised, risk-assessed, communicated and kept to the minimum necessary duration. Implement suitable temporary precautions and restore and test the affected equipment as required. If adequate protection cannot be maintained, work or occupancy may need to be restricted.

How can contractors prevent fires during building repairs?

Contractors should follow the approved work plan, use suitable equipment, control ignition sources, store flammable materials safely, maintain good housekeeping and report changing conditions. They should comply with permit requirements, keep escape routes clear and complete required inspections before leaving the work area.

Why is fire stopping important during building maintenance?

Fire stopping helps maintain the fire resistance of walls, floors and other compartment boundaries where pipes, cables and services pass through them. Unprotected openings can allow fire and smoke to spread into other areas. Affected penetrations should be restored using a suitable system installed in accordance with its requirements.

What should happen after maintenance work is completed?

Inspect the area, remove waste, complete required post-work checks, verify fire doors and compartmentation, and confirm that affected alarms and other systems are operational. Record defects, communicate outstanding actions and complete a formal handover.

How often should fire risks be reviewed during maintenance?

Review the risk assessment before work begins and whenever a significant change could affect fire safety. Site inspection frequency should reflect the hazards, duration and changing conditions. Higher-risk work may require more frequent checks or close supervision.

Can maintenance continue if a fire protection system is unavailable?

It depends on the system affected, the level of risk and whether adequate alternative precautions can be maintained. A formal assessment should determine whether work or occupancy can safely continue. If risks cannot be adequately controlled, the affected activity should be postponed or suspended until suitable protection is restored.

Conclusion: Make Fire Safety Part of Every Maintenance Task

Managing fire risks during building maintenance work requires planning, coordination and consistent supervision. Every maintenance activity should be assessed for its potential to introduce ignition sources, increase combustible loads, damage fire-resisting construction or reduce the performance of fire protection systems.

A practical approach combines a current fire risk assessment, task-specific planning, suitable hot work controls, safe material storage, effective contractor management, clear escape routes and reliable inspection and handover procedures.

The most important principle is to consider the whole building, not just the immediate work area. A repair can affect occupants, neighbouring rooms, shared escape routes and systems that other people depend on for their safety.

By applying these precautions consistently, building owners, facilities managers, supervisors and contractors can reduce avoidable fire risks, improve workplace fire safety and maintain safer premises during repair, refurbishment and routine maintenance.

Official Guidance and Further Reading

The following sources provide further information on fire safety during construction, workplace maintenance and fire risk assessment.

Important note: This article provides general fire safety information and is not a substitute for a site-specific fire risk assessment, competent professional advice or applicable legal requirements. Fire safety duties and technical standards vary by jurisdiction and building type. Confirm the requirements applicable to your premises and work before proceeding.